logo

products details

Created with Pixso. Home Created with Pixso. Products Created with Pixso.
Surge Protective Device
Created with Pixso.

Modular Surge Protective Device (SPD) For TN-C Systems (“3+0” Circuit) MYS5-385/20-3P (NS)

Modular Surge Protective Device (SPD) For TN-C Systems (“3+0” Circuit) MYS5-385/20-3P (NS)

Brand Name: XIWUER
Model Number: MYS5-385/20-3P (NS)
MOQ: 100
Price: Negotiable
Payment Terms: L/C,T/T
Supply Ability: 3,000,000 pcs a year
Detail Information
Place of Origin:
China
Certification:
ISO9001,ISO14001,ISO45001,CCC
SPD According To EN 61643-11:
Class 2
SPD According To IEC 61643-11:
Class II
AC Nominal Voltage (UN):
230/400 V (50/60 Hz)
AC Maximum Continuous Operating Voltage (Uc):
385 V (50/60 Hz)
Nominal Discharge Current (8/20 μs) (In):
20 KA
Maximum Discharge Current (8/20 μs) (Imax):
40 KA
Voltage Protection Level (Up):
≤ 1.9 KV
Operating Temperature Range (TU):
-40℃ To +70℃
Operating Status / Fault Indication:
Green/Red
Number Of Ports:
1
Minimum Installation Conductor Cross-section:
1.5 Mm² Solid Wire / Flexible Wire
Maximum Installation Conductor Cross-section:
35 Mm² Stranded Wire / 25 Mm² Flexible Wire
Main Terminal Screw Type / Torque:
M5 / 3.0 Nm ±10%
Mounting Method:
35 Mm DIN Rail, According To EN 60715
Housing Material:
Thermoplastic, UL 94 V-0
Installation Location:
Indoor
Degree Of Protection:
IP20
Dimensions:
See Figure Above
Remote Signaling Contact Type:
Floating Changeover Contact
AC Switching Capacity:
125 VAC / 1 A
DC Switching Capacity:
30 VDC / 0.5 A
Cross-sectional Area Of Remote Signaling Terminals:
0.2 Mm²
Remote Signaling Terminal Screw Type / Torque:
M2 / 0.25 Nm
Packaging Details:
Carton
Supply Ability:
3,000,000 pcs a year
Product Description

Function
The MYS5-385/20-3P (NS) is a modular surge protective device for TN-C systems. It uses a “3+0” circuit and is mainly used to discharge lightning and surge currents, limit transient overvoltages, and protect downstream low-voltage distribution equipment. Its nominal discharge current is 20 kA (8/20 μs), maximum discharge current is 40 kA, voltage protection level is ≤ 1.9 kV, and response time is ≤ 25 ns. The product has green/red operating/fault indication; the NS version also provides a floating changeover remote signaling contact for remote status monitoring and alarm.

Application
It is suitable for 230/400 V (50/60 Hz) TN-C AC low-voltage distribution systems, for indoor installation, and for 35 mm DIN rail mounting. It can be widely used in industrial, commercial, and civil building distribution cabinets, control cabinets, floor distribution boxes, and other occasions, especially in distribution systems requiring remote monitoring of SPD operating status.

Features

  • Complies with EN 61643-11 Class 2 and IEC 61643-11 Class II requirements

  • Maximum continuous operating voltage Uc: 385 V (50/60 Hz)

  • Nominal discharge current In: 20 kA; maximum discharge current Imax: 40 kA

  • Voltage protection level Up: ≤ 1.9 kV; response time tA: ≤ 25 ns

  • Modular 3P structure, 35 mm DIN rail mounting

  • Housing material: thermoplastic, UL 94 V-0; degree of protection: IP20

  • Operating temperature range: -40℃ to +70℃

  • Main terminal wiring: minimum 1.5 mm² solid wire/flexible wire, maximum 35 mm² stranded wire/25 mm² flexible wire; torque M5/3.0 Nm ±10%

  • NS version remote signaling contact: floating changeover contact, 125 VAC/1 A, 30 VDC/0.5 A; cross-sectional area of remote signaling terminal: 0.2 mm²; torque M2/0.25 Nm

  • Operating status/fault indication: green/red

Modular Surge Protective Device (SPD) For TN-C Systems (“3+0” Circuit)  MYS5-385/20-3P (NS)  

MYS5-385/20-3P (NS) Basic Circuit Diagram

Modular Surge Protective Device (SPD) For TN-C Systems (“3+0” Circuit)  MYS5-385/20-3P (NS)

MYS5-385/20-3P (NS) Dimensional Drawing